Asset Integrity — equipment safety assessment

LY/SB-106

Motor control centre 106

Report A-1029
Methodology v3.9
2024-12-28
Assessed risk
Critical
Highest score
15
Findings
3
Immediate
1
Coverage
15/15
Next due
2025-12-28

Stop use, isolate, escalate to the responsible engineer

Asset class
LV switchboard / distribution board
Facility
Lyndale Packing, Cranfield Way
Area
Utilities yard
Criticality
A
Manufacturer
Mainline Electrical
Model / serial
C503 / 37363-96
Installed
2009-07-01
Inspector
T. Fenwick

Findings (3)

R-SB-05Severe thermal rise at a terminationImmediate dangerS5 × L3 = 15Critical

Temperature rise at a termination is far beyond the alarm threshold and failure is imminent.

Action Shed load from the affected circuit now and remake the termination before the board is reloaded.

Arc flash / electric shock · due 2024-12-28 · NETA MTS §9.15

R-SB-02Blanking or gland plate missingNon-conformingS4 × L3 = 12High

An unused way or cutout is open, so the enclosure no longer provides its rated protection.

Action Fit correct blanks and gland plates. Do not use tape or sheet offcuts.

Arc flash / electric shock · due 2025-01-04 · IEC 61439-1 §8.4.2

R-SB-15Main switch not identifiedRecords / traceabilityS2 × L4 = 8Moderate

The main switch is not labelled, delaying isolation in an emergency.

Action Label the main switch with what it isolates, in durable marking.

Access, egress and emergency response impaired · due 2025-01-27 · AS/NZS 3000 §2.3.2

Assessment record

Identification and records · Board identifierLY-SB-106
Identification and records · Is a current single-line diagram available at the board?Yes
Identification and records · Is the circuit schedule present and matching the installed ways?Yes
Identification and records · Is an arc-flash / shock-hazard label fitted?Yes
Enclosure integrity · Do the doors close and lock as designed?Yes
Enclosure integrity · Are all unused ways blanked and gland plates complete?No
Enclosure integrity · Are any energised parts reachable without a tool?No
Enclosure integrity · Enclosure damageNone
Terminations and thermal condition · Months since last thermographic survey5 months
Terminations and thermal condition · Was a hotspot recorded above the alarm threshold?No
Terminations and thermal condition · Are cable terminations supported and strain-relieved?Yes
Protection and access · Months since residual current devices were tested8 months
Protection and access · Is the main switch identified and its function labelled?No
Protection and access · Clear working space in front of the board1518 mm
Protection and access · Is the working space free of stored material?Yes

The PDF is generated server-side from this same data — same findings, same wording, same methodology version, plus the photo plate and a sign-off block.