LV switchboard / distribution board · reassessed every 12 months · criticality A
Findings on the current assessment
from A-1029 · methodology v3.9Temperature rise at a termination is far beyond the alarm threshold and failure is imminent.
Action Shed load from the affected circuit now and remake the termination before the board is reloaded.
Arc flash / electric shock · due 2024-12-28 · NETA MTS §9.15
An unused way or cutout is open, so the enclosure no longer provides its rated protection.
Action Fit correct blanks and gland plates. Do not use tape or sheet offcuts.
Arc flash / electric shock · due 2025-01-04 · IEC 61439-1 §8.4.2
The main switch is not labelled, delaying isolation in an emergency.
Action Label the main switch with what it isolates, in durable marking.
Access, egress and emergency response impaired · due 2025-01-27 · AS/NZS 3000 §2.3.2
Assessment history
Historical assessments keep the methodology version they were completed under. Re-scoring old records against a newer version is an explicit action, never a side effect of publishing.
Asset record
- Tag
- LY/SB-106
- Asset id
- SB-106
- Class
- LV switchboard / distribution board
- Manufacturer
- Mainline Electrical
- Model
- C503
- Serial
- 37363-96
- Installed
- 2009-07-01
- Facility
- Lyndale Packing, Cranfield Way
- Area
- Utilities yard
- Facility manager
- D. Petrov
- Criticality
- A
What this class is assessed on
- Identification and records4 questions · photo + image analysis
- Enclosure integrity4 questions · photo + image analysis
- Terminations and thermal condition4 questions
- Protection and access4 questions
15 active rules · 7 vision cues.