NG/SB-101
Open assessment
Kestrel Process Group
Asset Integrity — equipment safety assessment

NG/SB-101

Compressor house distribution board 101

Report A-1024
Methodology v4.2
2026-06-28
Assessed risk
Critical
Highest score
15
Findings
4
Immediate
1
Coverage
15/15
Next due
2027-06-28

Stop use, isolate, escalate to the responsible engineer

Asset class
LV switchboard / distribution board
Facility
Northgate Works, Ardmore Industrial Estate
Area
Utilities yard
Criticality
C
Manufacturer
Cortec Systems
Model / serial
Q262 / 71642-23
Installed
2011-10-01
Inspector
M. Osei

Findings (4)

R-SB-05Severe thermal rise at a terminationImmediate dangerS5 × L3 = 15Critical

Temperature rise at a termination is far beyond the alarm threshold and failure is imminent.

Action Shed load from the affected circuit now and remake the termination before the board is reloaded.

Arc flash / electric shock · due 2026-06-28 · NETA MTS §9.15

R-SB-02Blanking or gland plate missingNon-conformingS4 × L3 = 12High

An unused way or cutout is open, so the enclosure no longer provides its rated protection.

Action Fit correct blanks and gland plates. Do not use tape or sheet offcuts.

Arc flash / electric shock · due 2026-07-05 · IEC 61439-1 §8.4.2

R-SB-12Enclosure does not secureNon-conformingS3 × L3 = 9Moderate

The enclosure cannot be closed and locked, so access is not restricted to authorised workers.

Action Repair or replace the door hardware and re-key the board to the electrical suite.

Arc flash / electric shock · due 2026-07-12 · AS/NZS 3000 §2.9.2

R-SB-06Thermographic survey overdueRecords / traceabilityS2 × L4 = 8Moderate

No thermographic survey has been recorded within the interval.

Action Book the survey while the board is under representative load, and file the report against the board identifier.

Loss of design or inspection traceability · due 2026-08-27 · NETA MTS §9.15

Assessment record

Identification and records · Board identifierNG-SB-101
Identification and records · Is a current single-line diagram available at the board?Yes
Identification and records · Is the circuit schedule present and matching the installed ways?Yes
Identification and records · Is an arc-flash / shock-hazard label fitted?Yes
Enclosure integrity · Do the doors close and lock as designed?No
Enclosure integrity · Are all unused ways blanked and gland plates complete?No
Enclosure integrity · Are any energised parts reachable without a tool?No
Enclosure integrity · Enclosure damageCosmetic
Terminations and thermal condition · Months since last thermographic survey38 months
Terminations and thermal condition · Was a hotspot recorded above the alarm threshold?No
Terminations and thermal condition · Are cable terminations supported and strain-relieved?Yes
Protection and access · Months since residual current devices were tested6 months
Protection and access · Is the main switch identified and its function labelled?Yes
Protection and access · Clear working space in front of the board1139 mm
Protection and access · Is the working space free of stored material?Yes

The PDF is generated server-side from this same data — same findings, same wording, same methodology version, plus the photo plate and a sign-off block.