Compressor house distribution board 101

LV switchboard / distribution board · reassessed every 12 months · criticality C

Latest report
Current risk
Critical
Stop use, isolate, escalate to the responsible engineer
Open findings
4
highest score 15
Last assessed
2026-06-28
by M. Osei
Next due
2027-06-28
On schedule

Findings on the current assessment

from A-1024 · methodology v4.2
Severe thermal rise at a terminationR-SB-05Immediate dangerS5 × L3 = 15

Temperature rise at a termination is far beyond the alarm threshold and failure is imminent.

Action Shed load from the affected circuit now and remake the termination before the board is reloaded.

Arc flash / electric shock · due 2026-06-28 · NETA MTS §9.15

Blanking or gland plate missingR-SB-02Non-conformingS4 × L3 = 12

An unused way or cutout is open, so the enclosure no longer provides its rated protection.

Action Fit correct blanks and gland plates. Do not use tape or sheet offcuts.

Arc flash / electric shock · due 2026-07-05 · IEC 61439-1 §8.4.2

Enclosure does not secureR-SB-12Non-conformingS3 × L3 = 9

The enclosure cannot be closed and locked, so access is not restricted to authorised workers.

Action Repair or replace the door hardware and re-key the board to the electrical suite.

Arc flash / electric shock · due 2026-07-12 · AS/NZS 3000 §2.9.2

Thermographic survey overdueR-SB-06Records / traceabilityS2 × L4 = 8

No thermographic survey has been recorded within the interval.

Action Book the survey while the board is under representative load, and file the report against the board identifier.

Loss of design or inspection traceability · due 2026-08-27 · NETA MTS §9.15

Assessment history

2026-06-28 · M. Osei
A-1024 · assessed under v4.2
4 findingsCriticalReport

Historical assessments keep the methodology version they were completed under. Re-scoring old records against a newer version is an explicit action, never a side effect of publishing.

Asset record

Tag
NG/SB-101
Asset id
SB-101
Class
LV switchboard / distribution board
Manufacturer
Cortec Systems
Model
Q262
Serial
71642-23
Installed
2011-10-01
Facility
Northgate Works, Ardmore Industrial Estate
Area
Utilities yard
Facility manager
H. Vance
Criticality
C

What this class is assessed on

  • Identification and records
    4 questions · photo + image analysis
  • Enclosure integrity
    4 questions · photo + image analysis
  • Terminations and thermal condition
    4 questions
  • Protection and access
    4 questions

15 active rules · 7 vision cues.