Kestrel Process Group
Asset Integrity — equipment safety assessment
LY/PV-106
Nitrogen buffer vessel 106
Report A-1010
Methodology v4.2
2026-05-28
Assessed risk
Moderate
Highest score
6
Findings
1
Immediate
0
Coverage
18/18
Next due
2027-05-28
Plan corrective work into the maintenance cycle
Asset class
Pressure vessel / air receiver
Facility
Lyndale Packing, Cranfield Way
Area
Compressor house
Criticality
B
Manufacturer
Halcyon Tank
Model / serial
S241 / 26300-63
Installed
2007-10-01
Inspector
M. Osei
Findings (1)
R-PV-13Pressure gauge missing or unreadableObservationS2 × L3 = 6Moderate
Operating pressure cannot be read at the vessel.
Action Fit a gauge spanning at least 1.5 times MAWP and mark the normal operating range on the dial.
Uncontrolled release of stored pressure · due 2026-06-27 · AS/NZS 3788 §5.7
Assessment record
Identification and records · Is the manufacturer's data plate present and legible?Yes
Identification and records · Design registration / plant numberPVR-26300
Identification and records · Maximum allowable working pressure853 kPa
Identification and records · Months since last internal inspection6 months
Identification and records · Is the pressure test within its interval?Yes
Pressure relief · Is a pressure relief device fitted?Yes
Pressure relief · Is the set pressure at or below MAWP?Yes
Pressure relief · Months since relief device certification36 months
Pressure relief · Discharge pathClear to safe area
Pressure relief · Is an isolation valve fitted between the vessel and the relief device?No
External condition · External corrosionLight
External condition · Are the visible weld seams free of cracking or undercut?Yes
External condition · Saddle and support conditionSound
External condition · Is the drain operable and the vessel free of standing condensate?Yes
Instrumentation and surrounds · Is a pressure gauge fitted and readable?No
Instrumentation and surrounds · Is the isolation point identified and accessible?Yes
Instrumentation and surrounds · Clear working space around the vessel990 mm
Instrumentation and surrounds · Is required signage in place?Yes
The PDF is generated server-side from this same data — same findings, same wording, same methodology version, plus the photo plate and a sign-off block.