Havenport Terminal · Compressor house

Steam separator 108

Pressure vessel / air receiver · reassessed every 12 months · criticality A

Latest report
Current risk
High
Act before the equipment is next relied upon
Open findings
4
highest score 12
Last assessed
2025-10-28
by P. Nakamura
Next due
2026-10-28
On schedule

Findings on the current assessment

from A-1015 · methodology v4.0
Relief discharge path obstructedR-PV-03Non-conformingS4 × L3 = 12

The relief device cannot discharge freely to a safe location.

Action Clear the discharge path and re-route it away from any walkway or work position.

Uncontrolled release of stored pressure · due 2025-11-04 · AS/NZS 3788 §5.6

Heavy external corrosion or section lossR-PV-06Non-conformingfrom photoS4 × L3 = 12

External corrosion has progressed to the point where remaining wall thickness cannot be assumed.

Action Arrange ultrasonic thickness testing at the affected areas and compare against the minimum design thickness before the next fill.

Structural failure under load · due 2025-11-11 · API 510 §6.3

Data plate missing or unreadableR-PV-10Records / traceabilityfrom photoS2 × L4 = 8

The vessel cannot be traced to its registered design data from markings on the equipment.

Action Recover the design registration from the plant register and fit a durable replacement plate carrying the registration number and MAWP.

Loss of design or inspection traceability · due 2025-12-27 · AS/NZS 3788 §4.4

Working space around the vessel restrictedR-PV-15Improvement opportunityfrom photoS2 × L3 = 6

There is not enough clear space to inspect, isolate or escape from the vessel position.

Action Clear and mark the working space around the vessel.

Access, egress and emergency response impaired · due 2025-12-27 · ISO 12100 §6.2.7

Assessment history

2025-10-28 · P. Nakamura
A-1015 · assessed under v4.0 · 1 photo
4 findingsHighReport
2024-10-28 · R. Aldridge
A-1014 · assessed under v3.9
1 findingModerateReport

Historical assessments keep the methodology version they were completed under. Re-scoring old records against a newer version is an explicit action, never a side effect of publishing.

Asset record

Tag
HP/PV-108
Asset id
PV-108
Class
Pressure vessel / air receiver
Manufacturer
Wessex Vessels
Model
Z905
Serial
96628-55
Installed
2007-05-01
Facility
Havenport Terminal, Dock Road
Area
Compressor house
Facility manager
S. Ilori
Criticality
A

What this class is assessed on

  • Identification and records
    5 questions · photo + image analysis
  • Pressure relief
    5 questions · photo + image analysis
  • External condition
    4 questions · photo + image analysis
  • Instrumentation and surrounds
    4 questions

16 active rules · 9 vision cues.