Plantsight
Engineering administration

Questionnaires

Sections, question wording, answer types, units, branching and photo steps — all data. Question ids are persistent, so history survives rewording and reordering.

4 sections18 questions4 questions no rule reads

Identification and records

pv.recordsphoto step: Nameplate and general arrangement5 questions

Establish what the vessel is and that its design and inspection history can be evidenced.

Is the manufacturer's data plate present and legible?
pv.nameplate.legiblebool
R-PV-10
Design registration / plant number
pv.design.regtext
recorded only, no rule reads it
Maximum allowable working pressure
pv.mawpnumberunit kPa
recorded only, no rule reads it
Months since last internal inspection
pv.internal.monthsnumberunit months
R-PV-12
Is the pressure test within its interval?
pv.hydro.currentbool
R-PV-11

Pressure relief

pv.reliefphoto step: Relief device and connection5 questions

The single most consequential system on the vessel.

Is a pressure relief device fitted?
pv.psv.fittedbool
R-PV-01
Is the set pressure at or below MAWP?
pv.psv.set.okbool

asked only when Is a pressure relief device fitted is yes

R-PV-05
Months since relief device certification
pv.psv.cert.monthsnumberunit months

asked only when Is a pressure relief device fitted is yes

R-PV-02
Discharge path
pv.psv.outletchoiceClear to safe area · Discharges toward walkway · Obstructed or capped

asked only when Is a pressure relief device fitted is yes

R-PV-03
Is an isolation valve fitted between the vessel and the relief device?
pv.psv.isolationbool

asked only when Is a pressure relief device fitted is yes

R-PV-04

External condition

pv.conditionphoto step: Shell, welds and supports4 questions
External corrosion
pv.corrosionchoiceNone · Light · Moderate · Severe
R-PV-06R-PV-07
Are the visible weld seams free of cracking or undercut?
pv.weld.conditionbool
R-PV-09
Saddle and support condition
pv.support.conditionchoiceSound · Surface corrosion · Section loss or cracking
R-PV-08
Is the drain operable and the vessel free of standing condensate?
pv.drain.operablebool
R-PV-14

Instrumentation and surrounds

pv.surrounds4 questions
Is a pressure gauge fitted and readable?
pv.gauge.okbool
R-PV-13
Is the isolation point identified and accessible?
pv.isolation.labelledbool
recorded only, no rule reads it
Clear working space around the vessel
pv.clearancenumberunit mm
R-PV-15
Is required signage in place?
pv.signagebool
recorded only, no rule reads it